OPTIMA plus 40




Data sheet OPTIMA plus 40

Input rating gross   40 kW  
Input rating net natural gas   36 kW  
Input rating net propane gas   37 kW  
Gas consumption natural gas (given 10,50 kWh/m³)   3,81 m3/h  
Gas consumption propane gas (given12,87 kWh/kg)   3,11 kg/h  
Length   7,090 mm  
Width   830 mm  
Gas hose connection to burner   1/2 inch  
Inlet gas pressure natural gas   min. 20 / max. 50 mbar  
Inlet gas pressure propane gas   min. 30 / max. 50 mbar  
Total weight   135 kg  
Recommended minimum mounting height (horizontal/wall mounted)   6,9 / 6,0 m  

OPTIMA plus 40